OUR SERVICES
Air scouring is the fastest, most water-efficient way to clean small to medium water mains. H&S Maintenance air scours 4 to 8 km of main in a six-hour shift, using your existing hydrants and valves, with no excavation. We have air scoured networks for water authorities and councils across Victoria and NSW since 2012.
Up to 300 mm
pipe diameter
4–8 km
cleaned per 6-hour shift
No excavation
uses existing hydrants and valves
Air scouring cleans a water main by pushing filtered, oil-free compressed air and controlled slugs of water through an isolated section of pipe. The air drives the water at high velocity, creating a scouring vortex. That vortex lifts sediment, biofilm, iron and manganese deposits and soft scale off the pipe wall and carries them out through a downstream hydrant.
We map the sections, confirm valves and hydrants, and support your customer notifications and traffic management plan.
We record free and total chlorine and turbidity, and run RPM testing where required.
The section is isolated between valves, and standing water is purged with high-volume, low-pressure air.
Controlled amounts of water are let in to form slugs. They travel through the main at high velocity, removing deposits.
Dirty water exits through a downstream hydrant until it runs clear, managed to protect stormwater and the environment.
Supply is restored and post-clean results are recorded and reported to you.
Air scouring compressor unit
Air filtration system on the air scouring unit
Filter bag collecting debris during air scouring
Clean water at the hydrant after the filter bag is removed
For mains above 300 mm, or where heavier deposits need mechanical cleaning, we recommend swabbing.
Every air scouring program includes pre- and post-cleaning testing for free chlorine, total chlorine and turbidity. We also offer Resuspension Potential Method (RPM) testing. A controlled flow increase at a hydrant measures how much sediment resuspends, which shows how dirty a main is before cleaning. RPM results let you rank zones by need and set evidence-based cleaning frequencies.
Usually a few hours per section. We clean each section once and restore supply as soon as the water runs clear.
Yes. Customers may briefly see milky water (trapped air) or notice a chlorine taste, both of which clear quickly.
Up to and including 300 mm diameter. Larger mains are better suited to swabbing.
It depends on source water and sediment load. RPM testing helps set a frequency for each zone.
Yes. Every program comes with section-by-section records and before-and-after water quality results.
Planning an air scouring program? Send us your network details for a quote.